Isolation Monitoring Device IMD100 is used to ensure safe energy transmission in connections between solar power plants and electrical grids, as well as in IT networks such as those found in hospitals. It continuously monitors the insulation resistance and, in the event of a potential fault, sends a signal to open or close the circuit breaker via its integrated relays, thereby protecting the network and ensuring safe operating conditions.
⚙️ Specification | Value |
---|---|
Supply Voltage | 24–380V AC/DC |
Power Consumption | 240 mW |
Operating Temperature | -25°C … +70°C |
Storage Temperature | -30°C … +70°C |
Protection Class | IP30 / IK-07 |
Nominal Voltage Range | AC 0–1 kV (0.1–460 Hz) / DC 0–1.3 kV |
Insulation Resistance Measurement Range | 1kΩ – 10MΩ |
Measurement Uncertainty | ±10% (min. ±1 kΩ) |
Display | 2.8” TFT-LCD Touch Panel |
Communication | RS-485 / MODBUS RTU supported |
Dimensions | 86 x 105 x 57 mm |
Weight | 270 g |
Connection & I/O Features |
---|
Power Input: 1 |
RS485 Connection: 1 (Galvanically Isolated, 2.5kV) |
Analog Measurement: 3 Phase + Neutral + Ground |
Relay Output: 2 (10A @ 230V AC) |
Digital Input: 4 (24 VDC, Optically Isolated) |
Functions |
---|
Two-Level Alarm: Adjustable as Warning and Trip |
LED Indicators: Power, Communication, Fault, Status |
Real-Time Monitoring: Digital bar display showing insulation resistance trend |
Touch Interface: User-friendly 2.8” TFT-LCD panel |
Areas of Use |
---|
Solar Power Plants |
Industrial Automation Systems |
Hydroelectric Power Plants |
Wind Power Plants |
IT Networks and Hospital Power Systems |
Why IMD100? |
---|
Detects insulation faults at an early stage |
Protects the grid or system components |
Provides safe intervention with automatic relay output |
Wide supply voltage range and flexible usage |
Supports remote monitoring via MODBUS RTU communication |