Bize Ulaşın

Field Case – The Busbar Could Have Exploded: PV Plant Insulation Monitoring

FIELD CASE STUDY — SOLAR PV INSULATION MONITORING

The busbar could have exploded. It was detected 3 weeks in advance.

A silent insulation fault at a solar power plant was detected and resolved thanks to the IMD100—without stopping the inverters or damaging any equipment. And why could a residual current device never detect it?

System
800 V AC - IT Network
Topology
String Inverter Solar Plant
Device
Inotel IMD100
Result
No production loss
TECHNICAL BACKGROUND

Why do residual current devices remain ineffective in IT networks?

In solar PV systems operating at an 800 V AC voltage level, the network topology is predominantly an IT (ungrounded) configuration. This means the transformer neutral is not connected to the operational ground.

In TT networks (residential, commercial buildings), when a conductor's insulation is damaged, a residual current occurs and the Residual Current Device (RCD) detects it instantly. In IT networks, however, this mechanism does not work—a single insulation fault does not generate a residual current.

TT AND IT NETWORK COMPARISON — WHAT HAPPENS DURING A FAULT?
TT Network Diagram

TT Network

Neutral is grounded. An insulation fault generates residual current, and the RCD trips the circuit.

IT Network 1st Fault Status

IT — 1st Fault

Neutral is isolated. No residual current during a single-phase fault. Only an IMD can detect it.

IT Network 2nd Fault Status

IT — 2nd Fault!

When the second phase is also damaged, a phase-to-phase short circuit occurs. Explosion, permanent damage, complete shutdown.

Solution: Insulation Monitoring Device (IMD) — The only solution to close this gap where residual current devices remain ineffective in IT networks is an IMD, which continuously measures the insulation resistance between live conductors and ground. It detects the first fault without shutting down the facility, giving the maintenance team time to respond.

SOLUTION

Inotel IMD100: The Silent Guardian of Solar PV Plants

IMD100

Inotel IMD100 — IT Network Insulation Monitoring Device

Continuous insulation resistance measurement in 800 V AC IT networks - Two-stage alarm outputs - Modbus Communication - DIN rail mounting - Field-proven success

Inotel IMD100 Product Image
Inotel IMD100 Display Interface
MEASUREMENT RANGE
1 kΩ — 10 MΩ
NOMINAL VOLTAGE
Up to 800 V
COMMUNICATION
Modbus RTU
ALARM OUTPUT
2 relays (NO/NC)
MOUNTING
35 mm DIN rail
DISPLAY
TFT touchscreen
The IMD100 screen displays real-time insulation resistance, time/date, alarm status, and communication status. The 3-week gradual decline observed in this case was monitored step-by-step through the IMD100's logging system, allowing the fault to be resolved before transforming into a busbar explosion.
REAL FIELD CASE STUDY

3-Week Early Warning: What Happened?

At a solar PV plant consisting of 800 Vac string inverters, the long-installed IMD100 began recording an unusual drop in insulation resistance measurements at the beginning of April.

EARLY APRIL — DAY 1

First alarm: Insulation resistance dropped continuously below 20 kΩ

The IMD100 detected that the system insulation resistance was persistently below 20 kΩ. It remained low regardless of day or night, and independent of climatic conditions such as rain, snow, or humidity. This indicated physical insulation degradation.

Alarm Active Inverters Operating Normally
WEEKS 1-2

Insulation resistance dropped below 10 kΩ — inverter startup times began to lengthen

Insulation resistance continued to decline. The inverters took longer to turn on in the morning, waiting more than usual; however, they eventually booted up and the plant continued to generate power.

Alarm Ongoing Startup Delay Present
WEEKS 2-3

Critical threshold: Below 4 kΩ — startup times lengthened critically

The resistance dropped below 4 kΩ. Startup times lengthened progressively; at the most critical stage, the inverters could only activate after very long standby periods.

Critical Level Startup Time Critically Extended
~3 WEEKS AFTER FIRST ALARM

The fault was localized and resolved

Following the continuous warning from the IMD100, the maintenance team physically located and repaired the insulation damage on the busbar between the transformer and the LV panel. No equipment suffered permanent damage.

Fault Resolved Zero Equipment Damage
3-WEEK DEGRADATION TREND OF INSULATION RESISTANCE
Week 1
~20 kΩ
Weeks 1-2
~10 kΩ
Weeks 2-3
<4 kΩ
Persistent low resistance = high insulation risk.

If the insulation alarm is ignored — real field damage examples

These photographs show the outcomes in cases where insulation faults went undetected and escalated. The IMD100 detects these conditions at their very onset.

In IT networks, residual current devices cannot detect insulation degradation. Without an IMD device, or if the alarm is ignored, damages similar to those below become inevitable.

Burnt cable insulation

Burnt cable insulation

Undetected insulation damage has caused the cable to burn completely.

Mechanical insulation damage

Mechanical insulation damage

Damage to underground cables caused by external factors.

Busbar/conductor thermal damage

Busbar/conductor thermal damage

Melting and burning in conductors where insulation degradation has escalated. The IMD prevents this outcome prior to a short circuit.

Cable installation damage

Cable installation damage

In solar PV plants, mechanical stress and environmental factors lay the groundwork for insulation degradation over time.

Note: The damages in these photos were caused by phase-to-phase short circuits or arcing. The IMD100 generates an alarm at the very beginning of the first insulation fault—allowing for intervention before reaching these catastrophic results.
SCENARIOS

What Would Happen Without the IMD100?

Insulation damage progressing on one phase could eventually affect another phase over time. The moment conduction began between the two phases, a phase-to-phase short circuit would be inevitable.

Without the IMD100

  • The residual current device remains silent
  • The fault grows invisibly
  • The second phase can also be damaged
  • Phase-to-phase short circuit — the busbar explodes
  • Permanent damage to the LV panel and/or transformer
  • The plant remains offline for an extended period
  • Massive financial loss + safety hazard

With the IMD100

  • Alarm triggered from Day 1
  • The plant remains in production for most of the 3 weeks
  • The maintenance team localized the fault
  • The busbar was physically repaired
  • The issue was resolved before a short circuit occurred
  • No equipment suffered permanent damage
  • Zero forced downtime, zero equipment damage
What could a residual current device do here? Nothing. No residual current is generated during a single phase-to-ground fault in an IT network. Circuit breakers would only trip the circuit after a phase-to-phase short circuit occurred and the busbar exploded—long after the damage was done.
3
weeks
early warning period
0
permanent equipment damage
0
forced plant downtime

Frequently Asked Question: Why doesn't the IMD automatically shut down the plant?

In IT networks, a first insulation fault is not dangerous unless a second phase is also damaged. If the IMD were to trip and shut down the plant at the first alarm, the plant would have been unnecessarily offline for 3 weeks in this case.

CORRECT USE

The IMD triggers an alarm, and the maintenance team takes action. The plant continues operating. The fault is resolved.

INCORRECT USE

If the IMD is wired to trip: The plant shuts down at the first drop in insulation, causing unnecessary production loss.

SECOND FAULT SCENARIO

If the alarm is ignored and a second phase is also damaged—a short-circuit fault can occur at this point in the facility.

CONCLUSION

Both production continuity and safety are optimized. The alarm → intervention → solution chain works seamlessly.

Is there insulation monitoring at your solar PV plant?

In solar PV plants with IT networks, the next busbar fault can grow silently without an IMD. A residual current device cannot detect this. Contact us for technical details, installation, and integration of the IMD100.

Request technical info →